dc.identifier.citationAnalysis of Air Exchange System Influence on Thermal and Concentration Modes in the Local Working Area under Radiant Heating Conditions / Boris Borisov, Geniy Kuznetsov, Vyacheslav Maksimov [et al.] // Frontiers in Heat and Mass Transfer (FHMT). — 2024. — Vol. 22, iss. 6. — P. 1597-1612.en
dc.identifier.urihttp://earchive.tpu.ru/handle/11683/139813-
dc.description.abstractThis study deals with the numerical investigation of combined heat transfer via conduction, laminar natural convection, and surface radiation in a closed rectagular cavity with a radiant heating source. Unsteady two-dimensional equations of mass, momentum, and energy conservation for complex heat transfer process under study were formulated in terms of the vorticity - stream function - temperature variables and solved by means of the finite difference method on a uniform grid. Developed numerical code was validated against two benchmark problems of convective and convective-radiative heat transfer. When analyzing complex heat transfer regularities, we varied the following parameters: dimensionless time 5<t<800, Rayleigh number 6*10^4<Ra<4*10^6, conduction-radiation number 19.71<Nr<78.84, surface emissivity 0.2<e<0.9, emitter length 0.1<D<1, walls thickness 0.05<M<0.25. According to the results of mathematical modelling, it was found that the radiant parameters significantly affected the formation of differential and integral characteristics of conjugate heat transfer. Along with that the convective Nusselt number was slightly changed in geometrical and physical conditions under study. An increase in the walls thickness led to a reduce in the temperature of the air cavity. However, the effect of wall thickness on the convective and radiative Nusselt numbers was not significanten
dc.format.mimetypeapplication/pdf-
dc.language.isoenen
dc.publisherGlobal Digital Centralen
dc.relation.ispartofFrontiers in Heat and Mass Transfer (FHMT). 2024. Vol. 22, iss. 6en
dc.rightsinfo:eu-repo/semantics/openAccess-
dc.rightsAttribution-NonCommercial 4.0 Internationalen
dc.rights.urihttps://creativecommons.org/licenses/by-nc/4.0/-
dc.sourceFrontiers in Heat and Mass Transfer (FHMT)en
dc.subjectgas infrared heateren
dc.subjectair exchange systemen
dc.subjectlocal working areasen
dc.subjecttemperature fieldsen
dc.subjectCO2 concentration fieldsen
dc.titleAnalysis of Air Exchange System Influence on Thermal and Concentration Modes in the Local Working Area under Radiant Heating Conditionsen
dc.typeArticleen
dc.typeinfo:eu-repo/semantics/article-
dc.typeinfo:eu-repo/semantics/publishedVersion-
dcterms.audienceResearchesen
local.description.firstpage1597-
local.description.lastpage1612-
local.filepathreprint-683801.pdf-
local.filepathhttps://doi.org/10.32604/fhmt.2024.056758-
local.filepathhttps://www.sciopen.com/article/10.32604/fhmt.2024.056758-
local.identifier.bibrec(RuTPU)683801-
local.issue6-
local.localtypeСтатьяru
local.volume22-
dc.identifier.doi10.32604/fhmt.2024.056758-
Располагается в коллекциях:Репринты научных публикаций

Файлы этого ресурса:
Файл РазмерФормат 
reprint-683801.pdf1,11 MBAdobe PDFПросмотреть/Открыть


Лицензия на ресурс: Лицензия Creative Commons Creative Commons